[1]贾勇勇,李玉杰,陶加贵,等.GW6B-252型隔离开关异常发热数值仿真与实验对比分析[J].高压电器,2020,56(03):240-246.[doi:10.13296/j.1001-1609.hva.2020.03.036 ]
 JIA Yongyong,LI Yujie,TAO Jiagui,et al.Numerical Simulation and Experimental Analysis on Abnormal Overheating of GW6B-252 High-voltage Disconnector[J].High Voltage Apparatus,2020,56(03):240-246.[doi:10.13296/j.1001-1609.hva.2020.03.036 ]
点击复制

GW6B-252型隔离开关异常发热数值仿真与实验对比分析()
分享到:

《高压电器》[ISSN:1001-1609/CN:61-11271/TM]

卷:
第56卷
期数:
2020年03期
页码:
240-246
栏目:
技术讨论
出版日期:
2020-03-15

文章信息/Info

Title:
Numerical Simulation and Experimental Analysis on Abnormal Overheating of GW6B-252 High-voltage Disconnector
作者:
贾勇勇 李玉杰 陶加贵 杨景刚 赵 科
(国网江苏省电力公司电力科学研究院, 南京 211103)
Author(s):
JIA Yongyong LI Yujie TAO Jiagui YANG Jinggang ZHAO Ke
(Jiangsu Electric Power Company Research Institute, Nanjing 211103, China)
关键词:
隔离开关 有限元仿真 过热分析 温升实验
Keywords:
disconnector finite element overheating analysis temperature rise experiment
DOI:
10.13296/j.1001-1609.hva.2020.03.036
摘要:
高压隔离开关异常发热一直是电力系统当中长期存在的安全隐患,系统研究其异常发热现象并采取一定的技术手段对其进行实时监测具有重要意义。文中以GW6B?252型高压隔离开关为例,通过有限元数值仿真模拟探究了不同接触电阻、不同负载电流及不同镀层材料等3种因素对隔离开关异常发热的影响,在此基础上,通过实验获取了不同接触压力、污秽程度、蚀点程度、镀层材料、负载电流作用下隔离开关稳态热点温升的分布特性。对比分析仿真与实验结果,提出了不同影响因素对隔离开关热点温升的影响程度或表现形式不同的结论,对隔离开关维护检修工作具有一定的指导意义。
Abstract:
The problem of overheating fault of high-voltage disconnector has brought unavoidable safety hazard for the power system. It is of great practical significance to study the phenomenon of abnormal overheating and take effective action to monitor it online. In this paper, GW6B-252 high-voltage disconnector is used as an example to explore the influence of contact resistance, load current and coating material on the abnormal overheating of the solation switch is investigated by finite element. Numerical simulation, which is the basis of the study on the steady hot spot temperature distribution of disconnector, and taking different contact pressure, contamination degree, the extent of corrosion point, coating material and load current into account. The simulations and the experiments are conducted, and the conclusion that the influence degree or manifestations of different factors on the hot-point temperature rise of isolation switch is distinct is made, which is of guiding significance to the maintenance of high-voltage disconnector.

参考文献/References:

[1] 崔景春,袁大陆,宋 杲. 高压隔离开关运行分析及其完善化[J]. 电器设备,2006(4):1-6. CUI Jingchun,YUA Dalu,SONG Gao. Analysis and improvement of high-voltage disconnector operation[J]. Electrical Equipment,2006(4): 1-6.
[2] 杨玉磊,李 博,张玉伟. 折臂式隔离开关分闸故障分析及改造方法[J]. 电气开关,2013(6):103-105. YANG Yulei,LI Bo,ZHANG Yuwei. Fault analysis and retrofitting of breaker-arm switch disconnector[J]. Electric Switch,2013(6): 103-105.
[3] 徐虎林. GW16型隔离开关结构的改进设计[J]. 电气制造,2011(50):2-5. XU Hulin. An improved design of GW16 disconnector structure[J]. Electric Manufacturing,2011(50): 2-5
[4] 夏振岭,宋维功,刘 峰,等. GW16-252 高压隔离开关不能分闸故障分析[C]//亚太智能电网与信息工程学术会议论文集. 北京:[s.n.],2011:203-205. XIA Zhenling,SONG Weigong,LIU Feng,et al. Fault Analysis of GW16-252 high voltage disconnector unusable to open a breakout[C]//Asia-Pacific Comference on Smrt Grid and Infornation Engineering. Beijing:[s.n.],2011:203-205.
[5] 吕念明,黄伟坚,胡 泰. 220 kV 变电站隔离开关静触头过热原因分析及解决方案[J]. 电工技术,2006(12):4. LYU Nianming,HUANG Weijian,HU Tai. AnalysisAnd solution of overheating of static contact of disconnector in 220 kV substation[J]. Electrician Technology,2006(12): 4.
[6] 吴 涛,余海涛,戴永正,等. 550 kV高压隔离开关热稳定性分析[J]. 高压电器,2013,49(9):134-141. WU Tao,YU Haitao,DAI Yongzheng,et al. Thermal stability analysis of 550 kV high voltage isolation switch[J]. High Voltage Apparatus,2013,49(9):134-141.
[7] 杨景刚,刘 媛,高 山. 等. 高压开关机械故障诊断技术[J]. 江苏电机工程,2016,35(2):1-5. YANG Jinggang,LIU Yuan,GAO Shan,et al. Review on mechanical fault diagnosis of high-voltaga circuit breakers[J]. Jiangsu Electrical Engineering,2016,35(2):1-6.
[8] TIMSIT R S. Electrical instabilities in stationary contacts:AI/AI and AI/brass junctions[C]//Proceedings of the Thirty Fourth Meeting of the IEEE Holm Conference on Electrical Contacts. [S. l. ]:IEEE,1988:12-16.
[9] RUNDE M,HODNE E,TTDAL B. Current-induced aging of contact spots[C]//Proceedings of the Thirty Fifth Meeting of the IEEE Holm Conference on Electrical Contacts. Chicago,IL,USA:IEEE,1989: 20-25.
[10] LEE K L,HU C K,TU K N. In-situ scanning electron-microscope comparison studies on electro-migration of Cu and Cu(Sn) alloys for advanced chip interconnects[J]. Journal of Applied Physics,1995(8): 4428-4437.
[11] 李广鹏. 隔离开关静触指组件热缺陷机理与防护研究[D]. 石家庄:石家庄铁道大学,2016. LI Guangpeng. Study on mechanism and protection of thermal defects of static contact components of isolating switches[D]. Shijiazhuang:Shijiazhuang Railway University,2016.
[12] 张 扬. 一例红外测温技术诊断220 kV隔离开关过热缺陷[J]. 电力工程技术,2012,31(5):21-22. ZHANG Yang,An example of diagnosing overheating defects in 220 kV disconnector by infrared thermometric tecniques[J]. Electric Power Engineering Technology,2012,31(5):21-22.
[13] 赵 科,李洪涛,杨景刚. 特高压GIS集中监造工作的若干思考[J]. 江苏电机工程,2016,35(2):69-71. ZHAO Ke,LI Hongtao,YANG Jinggang. Discussions on the centralized supervision of UHV GIS[J]. Jiangsu Electrical Engineering,2016,35(2):69-71.
[14] 梁方建,吴建辉,胡路东,等. 一起220 kV隔离开关电机开关误分事故分析[J]. 高压电器,2018,54(1):249-251. LIANG Fangjian,WU Jianhui,HU Ludong,et al. Analysis on a false tripping accident of motor of 220 kV disconnector[J]. High Voltage Apparatus,2018,54(1):249-251.
[15] 杨景刚,刘 媛,高 山. 等. 高压开关机械故障诊断技术[J]. 江苏电机工程,2016,35(2):1-5. YANG Jinggang,LIU Yuan,GAO Shan,et al. Review on mechanical fault diagnosis of high-voltaga circuit breakers[J]. Jiangsu Electrical Engineering,2016,35(2):1-6.
[16] 凌 颖,赵莉华,林 显,等. 高压隔离开关电触头性能改善探讨[J]. 高压电器,2010,46(8):101-105. LING Ying,ZHAO Lihua,LIN Xian et,Study on the performance improvement of the electric contact of high voltage isolation switch[J]. High Voltage Apparatus,2010,46(8): 101-105.

备注/Memo

备注/Memo:
收稿日期:2019-11-28; 修回日期:2020-01-20 基金项目:国家电网科技指南项目(高压开关设备机械状态评估及故障诊断关键技术研究)。 Project Supported by Research on the Key Technology of Mechanical State Evaluation and Fault Diagnosis of High Voltage Switchgear(Science and Technology Guide Project of State Grid Corporation of China).贾勇勇(1986—),男,高级工程师,从事电网设备状态分析及技术监督工作。 李玉杰(1991—),男,工程师,从事电力设备技术监督和开关设备状态检测工作。 陶加贵(1984—),男,高级工程师,从事电网设备状态分析及局部放电带电检测工作。 杨景刚(1984—),男,高级工程师,从事开关设备状态分析研究工作。 赵 科(1985—),男,高级工程师,从事开关设备状态评价及研究工作。
更新日期/Last Update: 2020-03-15