ZHOU Chun-yu1, LIU Zhen2, YU Fang2, et al. Influence of CVT Primary-Side Isolator Operation on Over-Excitation Protection of Transformer[J]. High voltageapparatus, 2009, 45(5): 112-115+118.
ZHOU Chun-yu1, LIU Zhen2, YU Fang2, et al. Influence of CVT Primary-Side Isolator Operation on Over-Excitation Protection of Transformer[J]. High voltageapparatus, 2009, 45(5): 112-115+118.DOI:
Capacitor voltage transformer(CVT) contains capacitors and nonlinear inductances
so primary-side isolator operation may cause abnormal secondary voltage to influences normal operation of relay devices in substation
or even to lead misoperations of over-excitation protection for main transformers.This paper establishes equivalent circuits models of CVT and the substation via ATP
and simulates CVT secondary voltage as primary-side isolator operates for determining the main factors which impact the amplitude of secondary voltage
and determining the reasons for misoperating over-excitation protection of main transformers.The result shows that misoperation of over-excitation protection for main transformers will not happen in normal operation.