SONG Yun-dong1, YUAN Shun1, ZHAO Chun-fang1. Calculation and Analysis on Ground-fault Neutral Point Voltage of Distribution Lines on Same Pole in Distribution Network[J]. High voltageapparatus, 2009, 45(3): 40-43.
SONG Yun-dong1, YUAN Shun1, ZHAO Chun-fang1. Calculation and Analysis on Ground-fault Neutral Point Voltage of Distribution Lines on Same Pole in Distribution Network[J]. High voltageapparatus, 2009, 45(3): 40-43.DOI:
For the distribution lines on same pole in a distribution network with neutral grounding
when single-phase grounding fault occurs in one system
the neutral point voltage transmits to the other normal system via coupling capacitor of distribution line on the same pole
and the voltage may result in the Peterson coil misoperation.In order to solve the problem
the main factors that affect the neutral point displacement voltage of the normal system are analyzed theoretically in this paper
the variations of the factors are obtained
and models of respective cable feeder lines substation and overhead lines substation are established.Therefore
the neutral point voltages of single-phase grounding fault and normal state are obtained by the models.If the length of the distribution lines on same pole is less than 5 km and other system parameters are set suitably
the Peterson coil misoperation induced by coupling capacitor doesn’t occur in the system.