500 kV tank circuit breaker has good anti-seismic performance
with an external line package type TA
compact configuration
small area and high reliability.However
in recent years
internal discharge faults of tank circuit breaker in Hebei Electric Power Corporation occurred frequently when 500 kV tank circuit breaker was being combined into grid.Through studying on fault phenomenon and experience from the laboratory
it is detected that internal discharge of tank circuit breaker is caused by impurities
so it is important to keep assembling condition clean and avoid the dropping of scraps during operation.At present
thoroughly cleaning up impurities at the bottom of tank circuit breaker is taken to keep inside cleaning.