Calculation and Analysis of a Switchgear Fault Caused by Lightning Strike on 220kV Transmission Lines[J]. High voltageapparatus, 2008, (5): 428-431.DOI:
Flashovers or even explosions of switchgears fixed on substations and power plant at the voltage rank of 220 kV or below
which were caused by lightning intrusive waves
have taken place frequently in east China in recent years.In July 2007
this kind of event occurred because of lightning strike on the 220 kV transmission line
which generated the circuit breaker flashover and current transformer dielectric breakdown.This paper simulates the accident considering the running condition
and obtains the lightning over-voltages by the software EMTP.According to the over-vohage values
the reasons of the accident are analysed
and some protection methods from over-voltage due to lightning intrusive wave are presented by installing MOAs at both ends of the 220 kV transmission lines.