LI De-jun1, SHEN Wei2, GUO Zhi-qiang2. Application Comparison between Conventional and Ultrasonic Detection Methods for GIS Partial Discharge[J]. High voltageapparatus, 2009, 45(3): 99-103.
LI De-jun1, SHEN Wei2, GUO Zhi-qiang2. Application Comparison between Conventional and Ultrasonic Detection Methods for GIS Partial Discharge[J]. High voltageapparatus, 2009, 45(3): 99-103.DOI:
Some popular technologies for detecting partial discharge(PD) in GIS are described.Some typical simulated defects during GIS operation
such as sharp protuberance on HV conductor
sharp protuberance on inner surface of housing
free particle
floating electrode
void in spacer
and metal particle stuck on insulator surface
etc.
were detected by means of the conventional pulse current detection and ultrasonic detection methods.The phase distributions of discharge pulse and ultrasonic wave pulse
the magnitudes of discharge on different defects under given voltage
and the features and magnitudes of root mean square and periodic peak values of ultrasonic waves from different defects
are respectively compared.The major features of the ultrasonic wave patterns from the two detection methods are hence achieved.These features may be taken as a reference for the application of ultrasonic detection of partial discharge to high voltage test and operation of GIS on site.