Abstract
According to the character of DC resistance measurement of power transformer windings
an automatic switch circuit of measured winding is presented to overcome the shortcoming of conventional transformer DC resistance instrument.In the measurement process
this technique needs only to change the transformer tap-switch
and the internal power relay automatically accomplishes the measurement of three-phase windings
which greatly decreases the intensity of the labor.An initiative discharge method is proposed to reduce inverse voltage peak in shortest time and protect the equipment and person.Moreover
Grubbs rule is applied to remove large error and a least squares formula of transformer DC resistance is also given.Test results show that the effects due to field interference and accidental error on measurement results can be minimized by using the Grubbs rule and least square formula of DC resistance.