WU Xu-tao1, AI Shao-gui2, LI Xiao-yan3, et al. The Test Study on Abnormal Fusing of the Primary Fuse for 35 kV Capacitor Voltage Transformer[J]. High voltageapparatus, 2009, 45(6): 102-105.
WU Xu-tao1, AI Shao-gui2, LI Xiao-yan3, et al. The Test Study on Abnormal Fusing of the Primary Fuse for 35 kV Capacitor Voltage Transformer[J]. High voltageapparatus, 2009, 45(6): 102-105.DOI:
often appears abnormal fuse of primary fuse during some system operating process.The test results show that in the process of the system operation
the voltage of the capacitor voltage transformer rapidly changes.During transient process
the LC circuit
consisted of linear capacitor
linear inductance and nonlinear inductance
produces the impulse current with higher amplitude and frequency
as well as the accumulation of the current thermal effect
leads primary fuse fusing.Through choosing higher rated current fuse
the abnormal fusing happening probability of the primary fuse can be reduced.According to the characteristic of the capacitor voltage transformer and the selecting principle of the capacitor voltage transformer fuse
cancel the primary fuse for 35 kV capacitor voltage transformer is reasonable.