糠醛浓度分析在电力变压器固体绝缘老化诊断中的应用
摘要
通过对基于固体绝缘老化诊断方法的对比
得出检测电力变压器油中糠醛浓度是评价固体绝缘老化状态的有效方法之一。在建立数学模型后
根据50台主变压器糠醛浓度的检测值
对其对数值与运行年限进行线性回归分析
确认了置信概率为99%的糠醛浓度的对数值的线性区间
从而有助于判断电力变压器固体绝缘的老化程度
这对实施变压器的状态检修有一定的指导作用。
Abstract
Comparing the methods of ageing diagnosis of solid insulation
it was found that measuring the furfural content in transformer oil is an effective method for evaluating the state of solid insulation ageing.After building a mathematical model
linear regression analysis was conducted for the logarithmic furfural content versus operating year based on the measured data of furfural contents in 50 main power transformers.The linear range of the logarithmic furfural content was determined with a fiducial probability of 99%.Consequently
the ageing degree of solid insulation in power transformer can be judged.