ZHANG Yuan-yuan1, ZHENG Hao2, SHI Rong1, et al. Absorbed Discharging Energy and Lightning Discharging Current Analysis of Surge Arresters on 35 kV Transmission Line[J]. High voltageapparatus, 2007, (2): 118-121.
ZHANG Yuan-yuan1, ZHENG Hao2, SHI Rong1, et al. Absorbed Discharging Energy and Lightning Discharging Current Analysis of Surge Arresters on 35 kV Transmission Line[J]. High voltageapparatus, 2007, (2): 118-121.DOI:
Based on the lightning overvoltage analysis model of transmission line
the absorbed discharging energy and lightning discharging current of line arresters on 35 kV transmission lines with and without shielding wires are analyzed by electromagnetic transient analysis program when the line surge arresters are applied to improve the lightning protection effect of transmission line.When the lightning respectively strikes on towers and transmission lines under varied conditions
such as different impulse grounding resistance and different lightning current
the lightning discharging current of arrester and the absorbed lightning discharging energy are calculated
and the influence of grounding resistance and lightning current on them are discussed.At the same time
the absorbed discharging energy and lightning discharging current are compared for 35 kV transmission lines with and without shielding wires in order to conclude the influence of shielding wires.