WANG Peng, ZHANG Gui-xin, LI Lian-zi, et al. Protection Methods for Electronic Current Transformer During Extreme Circumstance[J]. High voltageapparatus, 2007, (2): 136-139+142.
WANG Peng, ZHANG Gui-xin, LI Lian-zi, et al. Protection Methods for Electronic Current Transformer During Extreme Circumstance[J]. High voltageapparatus, 2007, (2): 136-139+142.DOI:
The performance of electronic current transformer could been deteriorated
even destroyed during some extreme circumstance
for example
overvoltage or over current.This paper introduces the protective problems of several parts for ECT
LPCT(low power current transformer)
Rogowski coil
power supply system and signal processing circuits in high-voltage side
the corresponding protective methods and design criterions have been proposed.Errors on LPCT induced by leakage current are analyzed.The analysis results show that errors induced by protection components could be ignored through selecting appropriate parameters.Type test results show the ECT based on the proposed methods meets IEC 0.2 class requirements
and the validity of the measures have been proved.