CAO Lin1, ZENG Rong1, ZHAO Jie2, et al. Study on the Influence of HVDC System Grounding Electrode Current on Power Transformer Operation[J]. High voltageapparatus, 2006, (5): 346-348+354.
CAO Lin1, ZENG Rong1, ZHAO Jie2, et al. Study on the Influence of HVDC System Grounding Electrode Current on Power Transformer Operation[J]. High voltageapparatus, 2006, (5): 346-348+354.DOI:
When HVDC system operates in monopolar mode and uses the earth as a return path
partial entering ground current may flow into the power transformers
which neutral point grounded
and this will bring a series unfavorable consequences to system operation and transformer. Using electromagnetic coupling method
this paper establishes model of the single-phase transformer with considering the variation of load
and analyzes the effects of such DC current on a single-phase core-form power transformer
such as increment of current harmonics and DC flux in the iron core. The simplified transformer model
under unloaded condition
is analyzed based on analytic method to verify its validity. Furthermore
the influence of different transformer operation status has also been discussed. The simulation results indicate that lower operation point can be more advantageous against the DC bias effects.