涿州220kV站40.5kV断路器与隔离开关间引线的技术改造
摘要
通过对涿州220kV站40.5kV断路器与隔离开关之间硬母线联接改造为软联接的实例
阐述了因断路器与隔离开关间为硬母线短距离联接导致的隔离开关动触头松动
渐渐脱离合闸位置的危害及分析解决该类问题的方法。
Abstract
This paper discusses the disadvantages of moving contact loosing
escaping from the closing position because of the hard bus connection between the circuit breaker and the disconnector. The improvement of reforming the hard bus connection to a soft one between 40.5 kV circuit breaker and disconnector is made in Zhuozhou 220 kV substation. The author also gives the method to solve this kind of problem.