大型整流机组由于存在稳流控制系统跟踪速度慢
饱和电抗器调压范围窄
△/Y侧饱和电抗器控制深度不平衡等缺陷
致使有载调压开关动作频繁
迫使压力保护动作
造成机组分闸。通过实践
在现有整流变压器外侧增加一套饱和电抗器
使调压范围达到60-70V
以提高电流平稳度并减少了有载调压开关动作次数。
Large-scale rectification set has some defects such that tracing speed of the steady current control system is slow
that adjusting voltage range of the saturable reactor is small
and that controlling depth of the saturable reactor at △/Y side is imbalance etc. These make the loaded switch adjust voltage frequently
force the pressure protector to act
and cause the apparatus tripping operation. A set of saturable reactor is added to rectification transformer
which makes the adjusting voltage range reach 60-70 V. Thus
steady current and reducing the action frequency of the loaded switch have been realized.