Determination of Arcing Time Difference during Short Line Fault Breaking for SF6 Circuit Breaker[J]. High voltageapparatus, 1996, (4): 3-6.DOI:
SF6断路器开断近区故障时燃弧时差的确定
摘要
通过对SF
6
断路器开断特性的模拟计算和近区故障开断的分析
提出了确定其开断近区故障时的燃弧时差的方法
并以LW6—110型SF
6
断路器为例
计算出了它开断近区故障时的燃弧时差
结果与试验相符很好。
Abstract
By means of the simulation of the breaking characteristics and the analysis of the Short Line Fault (SLF) breaking
the arcing time difference of SF6 circuit breaker when breaking SLF is determined. The results calculated from LW6 - 110 SF6 circuit breaker is well accordance with the test results.