Process Analysis of Double Circuit Transmission Line Trip-out on the Same Tower Due to Lightning[J]. 高压电器, 2011,47(9):31-36+43.
Process Analysis of Double Circuit Transmission Line Trip-out on the Same Tower Due to Lightning[J]. 高压电器, 2011,47(9):31-36+43. DOI: 10.13296/j.1001-1609.hva.2011.09.019.
DOI:
Process Analysis of Double Circuit Transmission Line Trip-out on the Same Tower Due to Lightning
摘要
In recent years
several failures of double circuit transmission line on the same tower due to lightning were happened in Beijing power grid.Although it can be reclosed successful
the lightning strike caused a grave threat to the power grid security.The cause of the accident and the accident process were studied for the sake of further understanding of the impact of lightning on power grid.As an example
110 kV double circuit transmission line(Xilong-line) was analyzed.At first
the system topology was given.Through the analysis on relay protection actions and the fault recorder data
over voltage on the insulator strings was calculated.Based on the analysis and the calculation
accident cause and the process were presented respectively.Secondly
it comes to the conclusion that the lightning failure was caused by counterattack.The wave of the lightning over voltage would spread to the not grounded neutral point of the transformers
and make the neutral protective gap breakdown
then cause freewheeling with the frequency of 50 Hz.As results of the relay protection
the double circuit transmission line all tripped out.Finally
the causes of the accident were proposed that included terrain features
large corner towers
strong thunderstorm weather and poor grounded contact of the tower.