WANG Dong, XIE Wei, FU Haijin, et al. Analysis on an Accident of Insulated Pull Rod of 550 kV Porcelain Column Circuit Breaker[J]. High voltageapparatus, 2015, 51(9): 177-181.
WANG Dong, XIE Wei, FU Haijin, et al. Analysis on an Accident of Insulated Pull Rod of 550 kV Porcelain Column Circuit Breaker[J]. High voltageapparatus, 2015, 51(9): 177-181. DOI: 10.13296/j.1001-1609.hva.2015.09.030.
An accident of an insulated tension pole of 550 kV porcelain column circuit breaker is introduced. After the accident
the primary and secondary equipments were checked
and tests both on site and in the manufacturing company were conducted for the circuit breaker to analyze the accident. It was found that the insulation defect of B-phase insulated pull rod resulted in partial discharge to gradually degrade the insulation of the circuit breaker
eventually leading to this accident. Therefore
it is necessary to draw up standard and put in practice for detection and judgment of number and size of air gap in insulated pull rod of a circuit breaker.