HUANG Shi, GAO Xiangxiang, LIU Haojun, et al. Calculation of di/dt at Current Zero and TRV PeakValue uc for Test-duty T100a[J]. High voltageapparatus, 2015, 51(10): 163-167+173.
HUANG Shi, GAO Xiangxiang, LIU Haojun, et al. Calculation of di/dt at Current Zero and TRV PeakValue uc for Test-duty T100a[J]. High voltageapparatus, 2015, 51(10): 163-167+173. DOI: 10.13296/j.1001-1609.hva.2015.10.027.
Because the computational complexity of the di/dt at current zero and TRV peak value ucfor asymmetric short-circuit current interruption
in this paper
the equivalent circuit models have been established for asymmetrical short-circuit fault breaking to gain the math expressions of di/dt at current zero and TRV peak value ucin the major loop and minor loop
in addition the di/dt and ucwith the same expression. By simplified the expression of ucin the appendix P of GB 1984—2014
the derived conclusion is verified which is right. Therefore
it can use the expression of di/dt to modify ucfor asymmetric short-circuit current interruption. The calculation results show that the correction error is proportional to the percentage of DC component p and the peak time t3
and Δucis increased when the time constant τ increasing. However
the error can meet the test requirements well. Finally
the calculated values of di/dt and Δucare given in this paper
which can provide the theory and reference basis for the test-duty T100 a.