FU Chenzhao, SI Wenrong, ZHU Lingyu, et al. Research on the Calculation Model for Transient Temperature Rise of Straight Buried Single-core Cable[J]. High voltageapparatus, 2018, 54(1): 158-163+169.
FU Chenzhao, SI Wenrong, ZHU Lingyu, et al. Research on the Calculation Model for Transient Temperature Rise of Straight Buried Single-core Cable[J]. High voltageapparatus, 2018, 54(1): 158-163+169. DOI: 10.13296/j.1001-1609.hva.2018.01.023.
A lumped parameter model is proposed to improve the calculation efficiency of transient temperature riseof buried single-core cable. In order to build the model without monitoring jacket temperature
balancing thermalresistance and inductance are used to simulate the time-variant characteristic in the process of thermal diffusion. Inthe case study
the temperature rise under the same condition is obtained respectively by the lumped parametermodel
finite element method
and CYMCAP. The comparative results show that the lumped parameter model isconsistent with the other two methods
which verifies the accuracy of the method proposed in this paper. Besides
themodel is optimized by building models considered the effects of cable heat and environment temperature
respectively
based on the superposition principle of heat conduction
so that the algorithm can adapt to the changeof environment temperature wells.