QI Weidong, YANG Ren, CUI Boyuan, et al. Operation Condition Assessment Method of 1 100 kV Column Filter Circuit Breaker Based on SF6 Decomposition Product[J]. High voltageapparatus, 2018, 54(2): 26-32.
QI Weidong, YANG Ren, CUI Boyuan, et al. Operation Condition Assessment Method of 1 100 kV Column Filter Circuit Breaker Based on SF6 Decomposition Product[J]. High voltageapparatus, 2018, 54(2): 26-32. DOI: 10.13296/j.1001-1609.hva.2018.02.005.
来评估频繁开合操作对灭弧室运行状态造成的影响。文中通过对某型1 100 k V滤波器用柱式断路器开展C2级试验
对试验后设备内部SF
6
分解产物进行检测、化学机理分析及设备解体检查
提出了通过检测CF
4
体积分数来评估1 100 k V滤波器用柱式断路器开合容性电流操作对灭弧室工况造成影响的方法
该方法可为其他SF
6
断路器的维护检修提供参考。
Abstract
The 1 100 k V column filter circuit breaker
as the electric production of the new high voltage equipmentindustry
is an important control and protection equipment of UHV power grid
and the arc of the opening and clos-ing process will cause the erosion of the contact and the nozzle arc chamber. With the increase of the opening andclosing times
the erosion becomes increasingly serious
which leads to the decline of the breaking ability. An effec-tive way should be presented to assess the frequent switching operation’s impact for the working condition of the arcextinguish chamber. In this paper
the C2 test is car
ried out on the 1 100 k V column filter circuit breaker. By detect-ing the SF
6
decomposition product
analyzing the chemical mechanism and examining the disintegration componentsof the equipment
a method is proposed that through detecting the content of CF
4
to assess the influence of capacitivecurrent switching operation on working condition of the arc extinguish chamber. The method can be used for the main-tenance and repair of the other SF