combination of electrical partial discharge detection and precise location is of great significanceto improve equipment maintenance efficiency. In this paper
some special cases GIS partial discharge pinpoint prob-lems
first
a new type of wideband UHF(0.7
4
GHz)equiangular spiral antenna sensor is developed
and compre-hensive treatment and delay times based on the weighted average of the positioning of the partial discharge waveformalgorithm are proposed
and a method for auxiliary confirmation of partial discharge defects based on X-ray excita-tion is established. Taking the spot location of GIS partial discharge defect in the 220 kV station
No. 2 transformer asan example
compared with the existing UHF location method
it has been proved that the integrated diagnosis meth-od proposed in this paper is more effective for the precise location of partial discharge in some special cases.