ZHU Qingcheng, LIU Zixun, LIU Wenxuan, et al. Arcing Duration and Erosion of CuW Contact Under DC Load and Different Surrounding Atmospheres[J]. High voltageapparatus, 2018, 54(9): 6-11.
ZHU Qingcheng, LIU Zixun, LIU Wenxuan, et al. Arcing Duration and Erosion of CuW Contact Under DC Load and Different Surrounding Atmospheres[J]. High voltageapparatus, 2018, 54(9): 6-11. DOI: 10.13296/j.1001-1609.hva.2018.09.002.
Surrounding atmospheres in hermetically sealed switching devices significantly affect their arc extinctionand electrical endurance. To better understand the effects of atmosphere on arcing duration and erosion of the con-tact
experiment was conducted with the CuW70 contact material under the DC supply voltage of 200
5
00V
the re-sistive load current of 40
1
50A
and the respective surrounding atmospheres of air
N
2
CO
2
and O
2
. It was found thatthe sequences of breaking arc duratiom for these atmospher
es changed with the supply voltage. O2 always had the lon-gest breaking arc duratiom
and N
2
showed shorter breaking arc duratiom than CO
2
in the case of 200
3
00V
but CO
2
showed shorter breaking arc duratiom than N
2
in the case of 400
5
00V. Experiment also indicated the anodes sufferedmass loss in all atmospheres