Pressure Rise Calculation and Pressure Relief Efficiency Analysis in the Cable Room of Switchgear Due to Internal Short-circuit Explosion[J]. High voltageapparatus, 2020, 56(10): 34-40.
Pressure Rise Calculation and Pressure Relief Efficiency Analysis in the Cable Room of Switchgear Due to Internal Short-circuit Explosion[J]. High voltageapparatus, 2020, 56(10): 34-40. DOI: 10.13296/j.1001-1609.hva.2020.10.007.
The three-phase short-circuit explosion experiment in the switchgear cable room is carried out
and the the change of arc power is obtained. Based on the transient dynamics analysis
the opening force and opening time of the pressure relief cover
and the ability of the door to withstand the overpressure are calculated. Under the condition of the pressure relief cover is close and open
the pressure rise distribution in the cable room is calculated.The pressure relief efficiencies of the pressure relief channel are analyzed when the pressure relief cover is opened with different angles
and the safety open angles of the pressure relief cover is gotten. The results indicate that the pressure rise is increased with the increase of arcing time
but the difference the pressure rise in different positions of the room gradually decreases. The pressure relief efficiencies of the pressure relief channel are increased with the increase of opening angles
and the pressure relief efficiency is 21% when the opening angle reaches 30°