ZHANG Xiaoxing, LIU Chang, ZHU Zhengyi, et al. Detection of C4F7N/CO2 Decomposition Products Based on FTIR[J]. High voltageapparatus, 2021, 57(3): 186-190+197.
ZHANG Xiaoxing, LIU Chang, ZHU Zhengyi, et al. Detection of C4F7N/CO2 Decomposition Products Based on FTIR[J]. High voltageapparatus, 2021, 57(3): 186-190+197. DOI: 10.13296/j.1001-1609.hva.2021.03.028.
采用傅里叶变换红外光谱仪与气相色谱—质谱仪对过热实验前后混合气体进行检测。研究发现约含300μL/L C
4
F
7
N的C
4
F
7
N/CO
2
混合气体在压强为0.100 MPa
温度为500℃
加热时长为10 h的实验条件下
利用FTIR检测到的C
4
F
7
N/CO
2
热分解产物有CO、C
3
F
6
。CO的红外吸收集中在2 000~2 220 cm
-1
波段;C
3
F
6
在1 000~1 100 cm
-1
、1 780~1 820 cm
-1
波段存在单个红外吸收峰
在1 180~1 250 cm
-1
、1 300~1 450 cm
-1
波段存在两相邻红外吸收峰。相关研究成果可为C
4
F
7
N型电力设备的故障诊断提供重要参考。
Abstract
The study on the decomposition characteristic of C
4
F
7
N/CO
2
can provide important technical reference forthe fault diagnosis of C
4
F
7
N/
CO
2
power equipment.The overheating experimental platform is set up to simulate theearly local overheating fault of C
4
F
7
N/CO
2
power equipment and the infrared detection platform is set up by FTIRtechnology.In order to improve the efficiency and accuracy of infrared qualitative analysis of C
4
F
7
N/CO
2
thermal de-composition products
the gas mixture before and after the overheating experiment is detected by fourier transforminfrared spectroscopy and gas chromatography-mass spectrometry.It is found by the study that the at the experimen-tal condition that C
4
F
7
N/CO
2
gas mixture containing about 300μL/L C
4
F
7
N at intensity of pressure at 0.100 MPa
thetemperature of 500℃and the heating time of 10 h has such thermal decomposition product as CO and C
3
F
6
whichis detected by FTIR.The infrared absorption of CO is concentrated in the 2 000~2 220 cm
-1
band;There is a singleinfrared absorption peak of C
3
F
6
in the 1 000~1 100 cm
-1
band
1 780~1 820 cm
-1
band
and two adjacent infraredabsorption peaks exist in the 1 180~1 250 cm
-1
band
1 300~1 450 cm
-1
band.The related study result can provideimportant reference for fault diagnosis of C