MA Feiyue, DING Pei, ZHU Hongbo, et al. Study on the Sensitivity of Layout 126 kV GIS Bus Bar Conductive Rod to Foreign Matter[J]. High voltageapparatus, 2021, 57(7): 37-45.
MA Feiyue, DING Pei, ZHU Hongbo, et al. Study on the Sensitivity of Layout 126 kV GIS Bus Bar Conductive Rod to Foreign Matter[J]. High voltageapparatus, 2021, 57(7): 37-45. DOI: 10.13296/j.1001-1609.hva.2021.07.006.
建立异物颗粒动态轨迹采集系统。研究表明126 k V GIS母线导电杆倒三角布置方式相比于正三角及侧三角方式
对固定异物引起电场强度畸变的程度更大
对可跳动异物跳动的高度更高、飞行时间更长
对GIS设备的危害性越大
侧三角布置方式次之
正三角布置方式相对不敏感。
Abstract
The layout of different conductive rod in GIS equipment has different degrees of sensitivity to foreign matter inside the enclosure.In this paper
such three typical layouts of conductive rod as positive triangle
inverted triangle and side triangle are taken as the base and the COMSOL is used to simulate the electric field strength of fixed foreign matter at the bottom of the enclosure.The dynamic trajectory collection system for foreign particles is set up through the analysis of the mechanical characteristics of pulsating foreign matter.The study shows that the inverted triangle layout of conductive rod of 126 kV GIS busbar
compared to positive triangle and side triangle
has a greater degree of distortion of the electric field strength due to fixed foreign matter
has a higher jumping height and longer flight time for beating foreign matter and greater hazard to the equipment.While
the side triangle layout is next and the positive triangle layout is relatively insensitive.