中国电力科学研究院有限公司,武汉 430074
国家电网有限公司,北京 100031
刘彬(1983—),女,教高,研究方向为智能传感与量测技术(通信作者)(E-mail:liubin@epri.sgcc.com.cn)。
收稿:2025-09-03,
修回:2025-12-06,
纸质出版:2026-05-16
移动端阅览
刘彬, 张民, 王庆, 等. 振动对压电陶瓷调制式全光纤电流互感器影响的试验研究[J]. 高压电器, 2026,62(5):132-140.
LIU Bin, ZHANG Min, WANG Qing, et al. Experimental Study on the Effect of Vibration on PZT Modulated Fiber-optic Current Transformer[J]. High Voltage Apparatus, 2026, 62(5): 132-140.
刘彬, 张民, 王庆, 等. 振动对压电陶瓷调制式全光纤电流互感器影响的试验研究[J]. 高压电器, 2026,62(5):132-140. DOI: 10.13296/j.1001-1609.hva.2026.05.015.
LIU Bin, ZHANG Min, WANG Qing, et al. Experimental Study on the Effect of Vibration on PZT Modulated Fiber-optic Current Transformer[J]. High Voltage Apparatus, 2026, 62(5): 132-140. DOI: 10.13296/j.1001-1609.hva.2026.05.015.
压电陶瓷(PZT)调制式全光纤电流互感器(FOCT)广泛应用在特高压直流工程中,对振动敏感是PZT调制式FOCT发生故障的主要原因之一。为研究振动对PZT调制式FOCT的影响,开展振动响应试验,分析不同振动激励对FOCT不同部件的影响。结果表明:振动对PZT调制式FOCT影响最大的部位为调制箱,其中的延时光纤是导致振动时FOCT输出异常的主要器件;当外界振动影响到延时光纤时,会产生非互易相位角,该相位角与Faraday相位角相互叠加,引入非互易相位误差;振动引起的误差与受振动干扰的光纤长度、干扰处距反射镜的时间延时、振动幅值、振动加速度均相关;提出的整体和局部振动响应试验方法可以有效考核PZT调制式FOCT的振动性能。文中的分析结果可为PZT调制式FOCT的振动试验方法、减振结构设计提供参考依据。
PZT modulated FOCT is widely used in UHVDC projects. Sensitivity to vibration is one of the main reasons for the failure of PZT modulated FOCT. For studying the influence of vibration on PZT modulated FOCT
the vibration response test is performed to analyze the influence of different vibration excitations on different parts of FOCT. The results show that the part mostly affected by vibration in the PZT-modulated FOCT is the modulatino box
of which the delay optical fiber is the main component that causes the abnormal output of FOCT during vibration. When the external vibration affects the delay optical fiber
a non-reciprocal phase angle is generated
which superimposes the Faraday phase angle and introduces the non-reciprocal phase error. The error caused by vibration is related to the length of the optical fiber interfered by vibration
the time delay between the interference and the mirror
the vibration amplitude and the vibration acceleration. The proposed overall and local vibration response test method can effectively evaluate the vibration performance of PZT modulated FOCT. The analysis results in this paper can provide reference for the vibration test method and vibration reduction structure design of PZT modulated FOCT.
王耀,赵玉灿,阎嫦玲,等.基于闭环算法的光学电流互感器的暂态电流误差特性研究[J]. 高压电器,2022,58(3):148-154.
WANG Yao,ZHAO Yucan,YAN Changling,et al. Study on transient current error characteristics of optical current transformer based on closed-loop algorithm[J]. High Voltage Apparatus,2022, 58(3):148-154.
刘博闻,邹国平,魏兴昌,等.用于过电压检测的电流互感器高频等效电路建模方法[J]. 高压电器,2023,59(3):156-162.
LIU Bowen,ZOU Guoping,WEI Xingchang,et al. Modeling method of high-frequency equivalent circuit of current transformer for overvoltage detection[J]. High Voltage Apparatus,2023,59 (3):156-162.
王中,李振华,成俊杰,等. Rogowski线圈电流互感器故障的早期诊断研究[J]. 高压电器,2023,59(2):162-168.
WANG Zhong,LI Zhenhua,CHENG Junjie,et al. Research on early diagnosis of fault of current transformer with Rogowski coil[J]. High Voltage Apparatus,2023,59(2):162-168.
李振华,陈兴新,蒋伟辉,等.基于弹性网络的空心线圈电流互感器误差预测[J]. 高压电器,2022,58(9):134-141.
LI Zhenhua,CHEN Xingxin,JIANG Weihui,et al. Error prediction of air-core-coil current transformer based on elastic network[J]. High Voltage Apparatus,2022,58(9):134-141.
周浪,刘水平,杨茜,等.防爆型油浸式电流互感器研制[J].电力电容器与无功补偿,2025,46(1):89-97.
ZHOU Lang,LIU Shuiping,YANG qian,et al.Development on explosion - proof oil - immersed current transformer[J]. Power Capacitor & Reactive Power Compensation,2025,46(1):89-97.
孙帆,王维庆,金铭,等.油浸型倒立式电流互感器内绝缘缺陷特征及检测方法[J].电力电容器与无功补偿,2025,46(2):120-126.
SUN Fan,WANG Weiqing,JIN Ming,et al.Inner insulation defect characteristic and detection method of oil immersed inverted current transformer[J]. Power Capacitor & Reactive Power Compensation,2025,46(2):120-126.
宋璇坤,闫培丽,肖智宏,等.全光纤电流互感器技术应用评述[J]. 电力系统保护与控制,2016,44(8):149-154.
SONG Xuankun,YAN Peili,XIAO Zhihong,et al. Comment on the technology and application of fiber optic current transformer(FOCT)[J]. Power System Protection and Control,2016,44(8):149-154.
袁亮,韩笑,郑拓夫,等.高速测量型全光纤电流互感器[J].计量与测试技术,2021,48(7):83-88.
YUAN Liang,HAN Xiao,ZHENG Tuofu,et al. High speed measurement type of fiber optical current transformer[J]. Metrology & Measurement Technique,2021,48(7):83-88.
HUANG Yuhao,XIA Li,PANG Fubin,et al. Self-compensative fiber optic current sensor[J]. Journal of Lightwave Technology, 2021,39(7):2187-2193.
HUANG Yuhao,HU Bei,PENG Shen,et al. Improving the computational efficiency of birefringent model based on equivalent matrix and modified permittivity[J]. Optics Communications,2021(488):126819.
阎嫦玲,罗苏南,文继锋,等.基于FARADAY旋光镜的光学电流互感器分析与试验研究[J]. 高压电器,2022,58(2):179-184.
YAN Changling,LUO Sunan,WEN Jifeng,et al. Study on analysis and test of optical current transformer based on FARADAY rotation mirror[J]. High Voltage Apparatus,2022,58(2):179-184.
胡蓓,肖浩,李建光,等.光纤电流互感器的噪声分析与信噪比优化设计[J]. 高电压技术,2017,43(2):654-660.
HU Bei,XIAO Hao,LI Jianguang,et al. Noise analysis and snr optimization design of fiber optical current transformers[J]. High Voltage Engineering,2017,43(2):654-660.
张敏杰.开环Sagnac干涉仪的数字信号处理[D]. 杭州:浙江大学,2016:12-16.
ZHANG Minjie. Digital signal processing for open-loop Sagnac interferometer[D]. Hangzhou:Zhejiang University,2016:12-16.
庞福滨,袁宇波,戴锋,等.全光纤电流互感器性能干扰因素分析及解决方案综述[J]. 高压电器,2022,58(7):64-72.
PANG Fubin,YUAN Yubo,DAI Feng,et al. Analysis of interference factors of all-fiber-current-transformer performance and summary of solutions[J]. High Voltage Apparatus,2022,58 (7):64-72.
高压直流输电系统直流电流测量装置第1部分:电子式直流电流测量装置:GB/T 26216. 1—2019[S].2019.
DC current measuring device for HVDC transmission system-Part 1:Electronic DC current measuring device:GB/T 26216. 1—2019[S].2019.
环境试验第3部分:试验导则地震试验方法:GB/T 2424. 25—2024[S].2024.
Environment testing Part 3:Test guidance-seismic test methods:GB/T 2424. 25—2024[S].2024.
环境试验第2部分:试验方法—试验Fc:振动(正弦):GB/T 2423. 10—2019[S].2020.
Environmental testing-Part2:Tests methods-Test Fc:Vibration (sinusoidal):GB/T 2423. 10—2019[S].2020.
互感器第6部分:低功率互感器的补充通用技术要求:GB/T 20840. 6—2017[S].2018.
Instrument transformers-Part 6:Additional general requirements for low-power instrument transformers:GB/T 20840. 6—2017[S]. 2018.
互感器第4部分:直流电流互感器的补充技术要求IEC 61869-14:2018[S].2018.
Instrument transformers - part 14:Additional requirements for current transformers for DC applications:IEC 61869-14:2018[S]. 2018.
ZHANG Hao. High temperature and vibration robustness all-fiber current sensor with a fiber-loop architecture and reflection scheme[J]. IEEE Photonics Journal,2017,9(3):1-8.
程嵩.线性双折射对全光纤电流互感器传感特性影响的研究[D]. 哈尔滨:哈尔滨工业大学,2016.
CHENG Song. The effect of linear birefringence on sensing characteristics of fiber optic current transformer[D]. Harbin:Harbin Institute of Technology,2016.
王立辉,何周,刘锡祥,等.反射式光纤电流互感器光波偏振态相互转换过程中的误差特性[J]. 电工技术学报,2013,28(1):173-178.
WANG Lihui,HE Zhou,LIU Xixiang,et al. Error characteristics in mutual conversion process of reflective fiber optic current transducer's optical polarization state[J]. Transactions of China Electrotechnical Society,2013,28(1):173-178.
SHI Songjie,LIU Zhanyuan,HOU Jibiao,et al. Insensitivity of fiberoptic current transducer to vibration[C]//Proceedings of Purple Mountain Forum 2019 International Forum on Smart Grid Protection and Control. Singapore:Springer Singapore,2020:497-504.
李绪友,郝金会,杨汉瑞,等.消除萨尼亚克光纤电流传感器振动干扰的光纤补偿环研究[J]. 中国激光,2012,39(2):119-123.
LI Xuyou,HAO Jinhui,YANG Hanrui,et al. Research on the compensating fiber loop for eliminating vibration in sagnac optic current sensor[J]. Chinese Journal of Lasers,2012,39(2):119-123.
KANG Menghua,WANG Yingli,XU Jintao,et al. Vibration immunity fiber optic current sensor employing a spun or twisted highly linear birefringence fiber[C]//Proceedings of the 32nd Chinese Control Conference. Xi'an:IEEE,2013:7468-7472.
刘力卿,马小光,李雪,等. 变压器绕组轴向振动模型及固有振动特性影响因素研究[J]. 高压电器,2023,59(4):149-155.
LIU Liqing,MA Xiaoguang,LI Xue,et al. Study on axial vibration model and influence factors of inherent vibration characteristics of transformer winding[J]. High Voltage Apparatus,2023,59(4):149-155.
林婧,张佳灏,黎旭,等. 基于振动信号的高压断路器螺栓松动故障诊断研究[J]. 高压电器,2023,59(3):28-33.
LIN Jing,ZHANG Jiahao,LI Xu,et al. Research on bolt looseness of high voltage circuit breaker based on vibration signal[J]. High Voltage Apparatus,2023,59(3):28-33.
鲁翔,陈向东,潘国洪,等.变压器—套管体系的动力模型及抗震加固分析[J]. 高压电器,2022,58(9):149-156.
LU Xiang,CHEN Xiangdong,PAN Guohong,et al. Dynamic model and seismic reinforcement analysis of transformer-bushing system[J]. High Voltage Apparatus,2022,58(9):149-156.
0
浏览量
4
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
陕公网安备 61010402000197