Severity Assessment of Air Gap Defect Discharge at GIS Solid Insulation Interface Under Constant Voltage
Research & Analysis|更新时间:2025-04-26
|
Severity Assessment of Air Gap Defect Discharge at GIS Solid Insulation Interface Under Constant Voltage
High Voltage ApparatusVol. 60, Issue 2, Pages: 62-68(2024)
作者机构:
华北电力大学高电压与电磁兼容北京市重点实验室,北京 102206
作者简介:
基金信息:
Science and Technology Project of State Grid Ningxia Electric Corporation of China (Research and Application of Reliability and Effectiveness Evaluation Technology of Partial Discharge State Detection Device)
TANG Zhiguo, LI Yang. Severity Assessment of Air Gap Defect Discharge at GIS Solid Insulation Interface Under Constant Voltage[J]. High voltage apparatus, 2024, 60(2): 62-68.
DOI:
TANG Zhiguo, LI Yang. Severity Assessment of Air Gap Defect Discharge at GIS Solid Insulation Interface Under Constant Voltage[J]. High voltage apparatus, 2024, 60(2): 62-68. DOI: 10.13296/j.1001-1609.hva.2024.02.005.
Severity Assessment of Air Gap Defect Discharge at GIS Solid Insulation Interface Under Constant Voltage
For studying the discharge development process of air gap defect
s at the interface of GIS insulators
a void air gap defect model is designed in this paper
and a long-term test platform for GIS air gap defect discharge is set up. Based on the breakdown voltage of the defect model
the AC constant voltages of 90%
U
b
60%
U
b
and 30%
U
b
are applied to the test sample with defects
and the UHF detection system is used to collect the discharge data until breakdown of the sample. The discharge state characteristics are analyzed by extracting the discharge times
amplitude and time interval
finding that there are two stages in the discharge development process of air gap defects of GIS. In the former stage
the discharge amplitude increases gradually
the discharge pulse is gradually sparse and the the discharge development is gradually stable. While
in the latter stage
the discharge amplitude decreases sharply
the discharge pulse is dense and the discharge development is drastic. The k-means clustering algorithm and BP neural network are used to set up the division rule of the partial discharge development stage of the air gap defect. The research shows that such three characteristic parameters as discharge times
amplitude and time interval show a trend of staged monotonicity. The absolute value of the forward difference of the three characteristic parameters can be used to assess the severity of GIS air-gap discharge of GIS. The cluster analysis of the GIS constant voltage test is performed to divide the discharge process into a stable deterioration stage and an accelerated deterioration stage. With the decrease of the applied voltage level
the stable deterioration stage is compressed and the proportion of the accelerated deterioration stage is increased.
Analysis on Power Quality Monitoring and Evaluation for Electrical Railway Load
Review on Aging Characterization and Evaluation of Silicon Rubber Composite Insulator
Theoretical Analysis of Dielectric Modulus Frequency Domain Characteristics and Its Application in the Evaluation of Water Content in Oil-paper Insulation
Environmental Adaptability Requirements and Insulation Performance Evaluation of Air-insulated Metal Enclosed Switchgear in Different Standard Systems
Related Author
ZHANG Jian-jun3
LIANG Dong3
ZHAO Liang1
XU Anjiu
ZHANG Suhua
REN Qiangde
MA Rong
ZHANG Guanjun
Related Institution
North China Electric Power University
Shijiazhuang Power Supply Company
Tangshan Power Supply
Sichuan Power Grid Guangyuan Power Supply Company
State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University