Mechanical Characteristics Analysis of New Type of Anti-interference Disconnector Under Wind Load
as the core equipment of the power transmission system
is often affected by the failure of closing operation due to interference of external wind force. Therefore
a kind of new type of anti-interference high voltage disconnector is designed. For studying the mechanical characteristics of the new disconnector under wind load further
firstly
the calculation model of wind field resistance torque of high voltage disconnector is constructed in Fluent software
and the resistance torque generated by the direction of wind field flow on the conducting rod is calculated. Then
the finite element model of the new disconnector is set up in the finite element software Ansys. Finally
the mechanical characteristics of the new disconnector are analyzed by applying the resistance torque generated by wind load to the simulation model. The results show that the deformation and stress concentration position of the disconnector are located in the pin hole of the support
which is judged to be the weak link of the disconnector
and on which the reinforcement treatment should be particularly considered. The simulation analysis mentioned above provides the basis for the wind resistance optimization design of the disconnector.