Fault Detection and Analysis on Closing Resistor of 1 100 kV GIS Circuit Breaker
The closing resistor of circuit breaker can effectively suppress the closing inrush current and switching over-voltage and play an important role in stable operation of power grid. The closing resistor will
once in case of fault and of correct operation and out of operation
causing huge equipment and safety accidents. Since the 1 100 kV GIS circuit breaker is of mostly multi-break structure
the coordination time sequence deviation across open contacts and the interference of contact bounce factor often lead to the characteristics of the closing resistor with no way to be measured
or the error of the test result is too large. As for such event that the pre-switching time and the resistance of the closing resistor of 1 100 kV GIS circuit breaker has no way to be detected
its structure and test principle are analyzed. It is concluded
through increasing the test frequency to obtain the complete test waveform
that one of the reasons that the pre-switching time and its resistance of the closing resistor have no way to be measured is the failure of across open contacts of closing resistor at one side. It is found through disassembly and inspection that the moving contact at one side of the closing resistor peels off due to breakage of the fixing bolt
and the conclusion that the operation characteristic has no way to be detected due to failure of open contacts of the resistor is verified. Finally
the corresponding suggestions and improvement measures are proposed from such aspects as manufacturing process
test items
test instruments and detection means
which can provide reference for process control and fault diagnosis of the same type of equipment.