Development and Project Application of Live Ice-melting System for UHVDC Transmission Lines
In order to avoid tripping of line due to ice coating and not affect operation of line in the ice melting
the live ice melting system for ultra-high voltage line ground wire and optical fiber composite overhead ground wire (OPGW)
including ice melting power supply
ice melting device
over-voltage protection system
OPGW and ground wire circuit
is developed. The check of OPGW/ground wire melting parameter and melting device parameter
type selection of transformers
smoothing reactors
bridge arm over-voltage protectors and design of the insulation transformation and insulation coordination of melting ice lines are performed
and an OPGW live melting ice system for ultra-high voltage lines is developed. The actual measurement at site shows that
in case the both ends of the ice melting circuit are open
the induced voltage of OPGW/ground wire can reach 13.7 kV. When the single end of the ice melting circuit is grounded
the induced voltage decreases to 0.6 kV. The calculation shows that the selected rated parameters of 10 kV/10 MW for the live ice melting device can meet the ice melting requirements at site. The surface icing of OPGW/ground wire is irregular
and the growth of ice length
diameter
and thickness is a nonlinear process. The actual measurement at site shows that after the ice melting device outputs a 260 A DC current for 75 minutes
the maximum temperature of OPGW rises to 20.7 ℃
completing safely the live ice melting of ultra-high voltage lines. The live ice melting system for OPGW of ultra-high voltage transmission lines developed in the paper provides a guarantee for safe operation of ultra-high voltage DC lines in rainy
Calculation and Measurement Analysis for Induced Voltage and Current of 500 kV/220 kV Mixed-voltage and Four-circuit Transmission Lines on the Same Tower
Analysis on Influence of Different Aluminum Sheath Structure on Electrical Characteristics of Cable
Characterization of Short-circuit Fault Voltage Distribution on Load Side of Cable-GIL Hybrid System
Analysis of loop current and temperature rise of GIS shell of ±200kV converter station based on field-circuit coupling
Simulation of Lightning Overvoltage in Substation Secondary System Based on ATP-EMTP
Related Author
HUANG Shiyang
NING Linru
CHEN Xiao
WANG Chenxing
LIN Tao
PENG Zhaowei
XU Dangguo
LI Yamei
Related Institution
Beijing Power Transmission and Transformation Co., Ltd.
State Grid Jibei Electric Power Co., Ltd.
State Grid Jibei Electric Power Co., Ltd. Electric Power Science Research Institute
State Grid Jiangsu Kunshan Electric Power Company Limited