Research on LC Oscillation Discharge Deicing Power Supply Based on Voltage Control
Research & Analysis|更新时间:2025-04-26
|
Research on LC Oscillation Discharge Deicing Power Supply Based on Voltage Control
High Voltage ApparatusVol. 60, Issue 4, Pages: 185-192(2024)
作者机构:
1.长沙理工大学电气与信息工程学院,长沙 410114
2.湖南信息学院电子科学与工程学院,长沙 410151
作者简介:
基金信息:
Key Laboratory of Ice Disaster Prevention of Guizhou Power Grid Co., Ltd.(GZ2015-2-0055);Key Scientific Research Project of Education Department of Hunan Province(19A018)
LI Yingxu, ZHOU Yusheng, ZHOU Wenqing, et al. Research on LC Oscillation Discharge Deicing Power Supply Based on Voltage Control[J]. High voltage apparatus, 2024, 60(4): 185-192.
DOI:
LI Yingxu, ZHOU Yusheng, ZHOU Wenqing, et al. Research on LC Oscillation Discharge Deicing Power Supply Based on Voltage Control[J]. High voltage apparatus, 2024, 60(4): 185-192. DOI: 10.13296/j.1001-1609.hva.2024.04.022.
Research on LC Oscillation Discharge Deicing Power Supply Based on Voltage Control
The skin effect of high-frequency current increases the heat loss caused by the current in the conductor
which provides a new technical method for
deicing on transmission lines. In this paper
a kind of high frequency deicing method based on
LC
oscillating discharge is proposed. The high frequency current is obtained by controlling the voltage square wave by using the characteristics of current change caused by capacitor charge and discharge when the
RLC
series circuit is converted from one to another steady state. This method can effectively reduce switching frequency of IGBT and reduce switching loss. According to the characteristics of IGBT
a set of deicing power supply is designed. The simulation experiments show that an effective deicing current of 1 kHz can be obtained for LGJ-400/50、LGJ-240/40、LGJ-120/25 and LGJ-70/10 of wire with lengths of 40 km and 35 km.