Discharge Defect of Free Metal Particle of 110 kV GIS Equipment and Its Disassembly Analysis
The analysis and treatment of abnormal ultrasonic wave in the disconnecting switch (DS) compartment of PT of 110 kV GIS is introduced. It is judged through amplitude location
time delay location and the change of equipment operation state that the defect is from the inside of the DS compartment. Multiple kinds of spectrum analysis on the partial discharge ultrasonic signal are performed
thinking that the free metal particle at the bottom the compartment is the main reason which causes abnormal ultra sonic wave signal. It is found by opening the enclosure that the grading cover of the stationary contact of the blade has obvious scratches and many black solid debris are at the bottom of the gas compartment. The weak installation process of the blade causes the metal debris to drop at the bottom of the gas compartment
generating partial discharge and causing the ultrasonic wave signal abnormal. The discharge of disconnecting switch of PT is a typical metal particle discharge case
which has provided experience and reference for the analysis of the similar abnormal situation in the future.