LIU Bin, DENG Xiaopin, LI Jianguang, et al. Research on Step Response Characteristics of Flexible DC Fiber-optic Current Transformer[J]. High voltage apparatus, 2024, 60(5): 140-146.
DOI:
LIU Bin, DENG Xiaopin, LI Jianguang, et al. Research on Step Response Characteristics of Flexible DC Fiber-optic Current Transformer[J]. High voltage apparatus, 2024, 60(5): 140-146. DOI: 10.13296/j.1001-1609.hva.2024.05.018.
Research on Step Response Characteristics of Flexible DC Fiber-optic Current Transformer
The conventional DC fiber-optic current transformer (FOCT) cannot meet the high-speed response requirements of flexible DC transmission engineering
so the step response characteristics of DC FOCT and its dynamic performance improvement methods need to be studied. In this paper
a comprehensive simulation
calculation and experimental study of its dynamic characteristics are performed in combination with the discrete mathematical model of the DC FOCT. The results show that the key parameters affecting the step response characteristics of DC FOCT are transit time
forward channel gain
filter order and communication delay. A step response test platform for DC FOCT is set up
and the step response rise time of the DC FOCT is less than 50 μs after parameter optimization
which meets the relevant application requirements.