Research on Electric Field Distribution of Insulators Based on Dynamic Pollution Accumulation of Charged Particles
Research & Analysis|更新时间:2025-04-26
|
Research on Electric Field Distribution of Insulators Based on Dynamic Pollution Accumulation of Charged Particles
High Voltage ApparatusVol. 60, Issue 5, Pages: 147-155(2024)
作者机构:
1.国网甘肃省电力公司,兰州 730030
2.兰州交通大学自动化与电气工程学院,兰州 730070
3.兰州交通大学甘肃省轨道交通电气自动化工程实验室,兰州 730070
作者简介:
基金信息:
National Natural Science Foundation of China(52167019;51867012);Science and Technology Project of State Grid Gansu Electric Power Research Institute(52272219000Q)
LI Chengxue, LYU Banghuan. Research on Electric Field Distribution of Insulators Based on Dynamic Pollution Accumulation of Charged Particles[J]. High voltage apparatus, 2024, 60(5): 147-155.
DOI:
LI Chengxue, LYU Banghuan. Research on Electric Field Distribution of Insulators Based on Dynamic Pollution Accumulation of Charged Particles[J]. High voltage apparatus, 2024, 60(5): 147-155. DOI: 10.13296/j.1001-1609.hva.2024.05.019.
Research on Electric Field Distribution of Insulators Based on Dynamic Pollution Accumulation of Charged Particles
For studying the influence of charged pollution particles on the surface pollution and electric field distribution of insulators as well as the corona discharge phenomenon in the air domain
the FXBW-35/70 insulator is taken as the study object
the coupling wind tunnel model of AC-DC
turbulence
charged particle interaction and particle motion is constructed by using the multi-physics coupling finite element software Comsol Multiphysics
and the distribution of corona discharge by charged particles on the surface of insulators
electric field and air domain is studied. The result shows that the higher the wind speed
the faster the pollution accumulation speed in the windward area compared to other areas
the larger the particle size
the more severe the pollution in the windward area
the less pollution in the leeward area
and the little change in the crosswind area. The surface potential and electric field distortion of the shed in the windward area are the most severe during pollution
followed by the leeward area. After pollution
the surface potential and electric field of the shed have eased
and the windward area is more severe than the leeward area. During the pollution
there is a risk of corona discharge in the air around a large and small shed near the high-voltage and low-voltage ends
and the first large shed near the high-voltage and low-voltage ends will experience corona discharge. After the pollution
there is a risk of corona discharge within 1mm at the root of large shed of low voltage side
and also round the whole large shed of the high voltage side as well as the root of the small shed.