Fault Location of DC Cable Based on S-transform Mode Energy Analysis
Research & Analysis|更新时间:2025-04-26
|
Fault Location of DC Cable Based on S-transform Mode Energy Analysis
High Voltage ApparatusVol. 60, Issue 7, Pages: 201-209(2024)
作者机构:
1.长沙理工大学电气与信息工程学院,长沙 410114
2.金杯电工衡阳电缆有限公司,湖南 衡阳 421007
作者简介:
基金信息:
National Natural Science Foundation of China(51977014);Natural Science Foundation of Hunan Province(2020JJ6054);Key Scientific Research Project of Hunan Provincial Department of Education(22A0230)
XIA Xiangyang, LIU Yixuan, LIU Xiong, et al. Fault Location of DC Cable Based on S-transform Mode Energy Analysis[J]. High voltage apparatus, 2024, 60(7): 201-209.
DOI:
XIA Xiangyang, LIU Yixuan, LIU Xiong, et al. Fault Location of DC Cable Based on S-transform Mode Energy Analysis[J]. High voltage apparatus, 2024, 60(7): 201-209. DOI: 10.13296/j.1001-1609.hva.2024.07.022.
Fault Location of DC Cable Based on S-transform Mode Energy Analysis
In view of such issues as low accuracy of fault location and and weak generalization ability of location model in the fault location method of existing high voltage DC cable
a kind of fault location method of time-frequency domain energy analysis is proposed with consideration of the characteristics of rich fault information in the transient signal generated by the fault point after the fault of the cable. The method uses the characteristics of multi-class support vector machine to construct a DC cable fault location model
uses the DC cable phase mode decoupling matrix to decouple the electrical parameters of the cable
and adopts the S-transform to perform time-frequency domain conversion. The obtained modulus is used to construct mode energy and is used as the sample to trains the SVM model. The experimental results show that the proposed method can accurately measure the distance of different types of faults under different transition resistances and different locations.