Analysis of Different Realization Modes and Auti-short-circuit Performance of High Impedance Transformer
The typical three winding 240 MVA/220 kV power transformer
which is used widely in power system
is taken as an example
the working principle and four typical structural characteristics of high impedance transformer are described
the short-circuit resistance under different short-circuit conditions is analyzed
the short-circuit resistance performance of three high impedance transformers with typical structures is compared and analyzed and the pros and cons of the short circuit performance of the high impedance transformer is assessed. The results show that the high impedance transformer with high-voltage built-in and series reactance structure has good short-circuit resistance performance
and the series reactance structure has more advantages in the axial force and the compressive stress of high
medium and low winding
the circumferential stress of regulating winding
the end axial force of transformers and the overall short-circuit resistance is the best.