Research on Switching Reignition Over-voltage of Compensation Capacitor Bank Based on Series Nonlinear Resistor Combination Switch
Research & Analysis|更新时间:2025-04-26
|
Research on Switching Reignition Over-voltage of Compensation Capacitor Bank Based on Series Nonlinear Resistor Combination Switch
High Voltage ApparatusVol. 60, Issue 8, Pages: 183-192(2024)
作者机构:
1.内蒙古超高压供电公司,呼和浩特 010080
2.西安交通大学电气工程学院,西安 710049
作者简介:
基金信息:
Science and Technology Project of Inner Mongolia Power (Group) Co., Ltd. (Research on Automatic Early Warning System for Faults of Reactive Power Compensation Devices)
LIU Bin, YUE Yonggang, ZHANG Qingru, et al. Research on Switching Reignition Over-voltage of Compensation Capacitor Bank Based on Series Nonlinear Resistor Combination Switch[J]. High voltage apparatus, 2024, 60(8): 183-192.
DOI:
LIU Bin, YUE Yonggang, ZHANG Qingru, et al. Research on Switching Reignition Over-voltage of Compensation Capacitor Bank Based on Series Nonlinear Resistor Combination Switch[J]. High voltage apparatus, 2024, 60(8): 183-192. DOI: 10.13296/j.1001-1609.hva.2024.08.022.
Research on Switching Reignition Over-voltage of Compensation Capacitor Bank Based on Series Nonlinear Resistor Combination Switch
This paper aims to study the over-voltage in case of switching the parallel reactive power compensation capacitor banks in the power system. The switching capacitor bank model is set up through ATP-EMTP software and the over-voltage level of both general switch and series resistor switch is simulated under various conditions. For solving the problem of the ineffectiveness of series resistor switch in limiting two-phase reignition at two times
a solution using a series non-linear resistor combination switch is proposed
and the effects of the three schemes in limiting the over-voltage are compared. The simulation results show that the series nonlinear resistor combination switch shows excellent limiting effect under two-phase reignition conditions at two times
can effectively suppress the over-voltage and protect insulation of the capacitor bank. The combination switch can be used as a reference for the design of reactive power compensation system for shunt capacitor bank in power system.