ZHANG Xingyu, WANG Yanwei, AN Yiyan, et al. Development of Micro-moisture Content Detection Device of C4F7N Gas Mixture Based on Tunable Laser Technology[J]. High voltage apparatus, 2024, 60(8): 238-244.
DOI:
ZHANG Xingyu, WANG Yanwei, AN Yiyan, et al. Development of Micro-moisture Content Detection Device of C4F7N Gas Mixture Based on Tunable Laser Technology[J]. High voltage apparatus, 2024, 60(8): 238-244. DOI: 10.13296/j.1001-1609.hva.2024.08.028.
Development of Micro-moisture Content Detection Device of C4F7N Gas Mixture Based on Tunable Laser Technology
N gas mixture is an environmentally friendly insulating alternative gas to SF
6
for new electrical equipment. C
4
F
7
N gas mixture
in case of being used as an insulating gas in high-voltage equipment
has similar problems with SF
6
equipment
and the quality of the gas mixture affects normal operation of the equipment. The C
4
F
7
N gas mixture
in case of moisture exceeding the limit
is likely to occur such problem as reduction of insulation performance of equipment due to discharge. It is therefore particular important to develop the operation
maintenance and detection device for the use of C
4
F
7
N gas mixture. In this paper
the quantitative detection technology of micro moisture content in C
4
F
7
N by tunable laser
infrared absorption spectroscopy is mainly studied. The spectroscopy theory of the tunable laser
the principle of harmonic detection and the infrared absorption characteristics of moisture are studied
and the influence of C
4
F
7
N as background gas on the accuracy of micro moisture detection is introduced. Then
the TDLAS structure design
hardware design and type selection are introduced. The DFB laser is used to design and manufacture the photoelectric conversion module
the light source driving module
the infrared multiple reflection pool
the circuit as well as software parts. The micro-moisture detection device for C
4
F
7
N gas mixture is developed based on the tunable laser
which removes the influence of interference components
improves the accuracy of micro moisture detection and can detect a low limit down to 1 μL/L. The performance results of the device show that it meets standard requirement
has high accuracy of quantitative detection of micro-moisture
and is beneficial to the correct judgment of the operating state of the equipment.