Synchronization Test Technology for Line Merging Units Based on Voltage Following
The accuracy of the data information collected and transmitted by the merging unit determines whether the smart substation protection can operate reliably
which in turn affects safe operation of the system. In view of the requirement of verifying the line merging unit under online operation of the bus merging unit
a synchronization test technology for line merging units based on voltage following is proposed in this paper. By designing an in-phase follower
a current signal with adjustable amplitude is generated
amplified into current calibration via power so to provide the measurement signal and the measurement feedback is taken as the current calibration benchmark. At the same time
the Prony algorithm is used to calculate the secondary amplitude of the bus voltage and phase
which is used as the voltage calibration reference. For verifying the feasibility of the synchronization test technology
a laboratory test platform test based on RTDS is designed. The results show that this technology greatly reduced the synchronization test and debugging process of the merging unit