Simulation Analysis on Influence of Current Frequency on Breaking Capacity of Vacuum Circuit Breaker
With the development of such new energy as wind power as well as DC power grid
the frequency of the breaking current of circuit breaker is diversified
which requires the circuit breaker can break the current higher or lower than 50 Hz. For this problem
the influence of current frequency on the breaking capacity of vacuum circuit breaker is studied from such three aspects as arcing process
magnetic field regulation and post-arc process in this paper. Firstly
the distribution of arc micro parameters at different frequencies is studied. It is found that with the increase of frequency
the arc configuration presents the phenomenon of agglomeration
and the contact presents the phenomenon of serious local ablation. However
the total ablation of the contact becomes smaller due to the shorter arcing time. The lower the frequency
the longer the arcing time
and the contacts show serious ablation. Then
the magnetic field distribution of cup-shaped longitudinal magnetic contacts under different frequencies is studied. It is found that with the increase of frequency
the more uneven the magnetic field distribution is
the less the diffusion effect on the arc plasma becomes
and the plasma is more difficult to diffuse due to the shortening of arcing time. Finally
it is found through the analysis of the influence of frequency on the growth process of back arc sheath that the greater the frequency
the slower the back arc sheath grows to the full opening distance
thus reducing the breaking capacity. It is concluded that the contact of the circuit breaker under low frequency is seriously ablated as a whole
and a large amount of metal vapor will be generated when the arc is extinguished. The attenuation process of metal vapor will dominate the post arc insulation recovery process of the circuit breaker
while the post arc insulation recovery process of the circuit breaker under high frequency is dominated by the sheath growth process.