Study on Flicker Detection Measurement Method of DC Distribution System
Technical Discussion|更新时间:2025-04-26
|
Study on Flicker Detection Measurement Method of DC Distribution System
High Voltage ApparatusVol. 60, Issue 10, Pages: 198-205(2024)
作者机构:
1.国网河北省电力有限公司电力科学研究院,石家庄 050000
2.西安博宇电气有限公司,西安 710065
作者简介:
基金信息:
Science and Technology Project of the State Grid Hebei Energy Technology Service Co., Ltd. (Research on Power Quality Testing Technology and Device Development for Low Voltage DC Distribution Network in Xiong’an New Area)
SU Can, ZHOU Wen, HU Xuekai, et al. Study on Flicker Detection Measurement Method of DC Distribution System[J]. High voltage apparatus, 2024, 60(10): 198-205.
DOI:
SU Can, ZHOU Wen, HU Xuekai, et al. Study on Flicker Detection Measurement Method of DC Distribution System[J]. High voltage apparatus, 2024, 60(10): 198-205. DOI: 10.13296/j.1001-1609.hva.2024.10.021.
Study on Flicker Detection Measurement Method of DC Distribution System
the DC voltage and DC current characterizing feature of DC distribution system is changing instantaneously in random in terms of fluctuation magnitude and frequency
making variation of illuminance of lights connected to DC network
leading to human being impression of unsteadiness of visual sensation induced by a light stimulus
namely flicker. Comparing with the recognized and standardized flicker measurement method of AC distribution system
the flicker measurement method for DC distribution system is still under development and discussion. In this paper
a new method called non-squaring-demodulation method applicable for DC distribution system is proposed on the basis of the feature of DC distribution system and the traditional squaring-demodulation flicker measurement method defined in AC distribution system. The simulation analysis shows that the method is high in accuracy
the error within the wide flicker variation range is within the acceptable range
which is greatly superior to traditional square demodulation method.