Study on Temperature Distribution of Epoxy Insulated Power Electronic Transformer Based on Fluid-solid-structure Coupling
Hot spot temperature is an important parameter which directly affects insulation life of power electronic transformer. For guiding reasonably insulation epoxy encapsulation design of the power electronic transformer
the equivalent model of 220 kW/30 kHz power electronic transformer is constructed
and the influence of the thermal conductivity of epoxy insulating material on temperature distribution characteristic of transformer at different operation conditions. The results show that the hot spot temperature of power electronic transformer with coaxial distribution of high and low voltage windings is mainly located at the height which is 56% from the bottom of winding
and it gradually increases with the increase of load coefficient. In the case of short circuit
the hot spot temperature of high and low voltage windings rises at the speed of 8 ℃/s and 22 ℃/s respectively. The hot spot temperature of the transformer decreases significantly with the increase of the thermal conductivity of the epoxy insulating material. When the thermal conductivity of the epoxy insulating material is higher than 1.1 W/(m·K)
the hot spot temperature variation tends to be gentle. At this time
the temperature distribution of the transformer meets the requirements of China national standard GB/T 1094.11—2022 specification and has a load margin of 30%. The research work can provide theoretical reference for the design of epoxy insulation encapsulation of power electronic transformer.
Study on Seismic Performance Improvement Methods for Gas-insulated Transmission Lines (GIL) in Ultra-high Voltage Converter Station
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Analysis of Maximum Compression Displacement and Fatigue Life of Bellows
Vibration Response Analysis of 220 kV Mobile Load Transfer Device Based on Ansys Workbench
Related Author
YANG Rui
SI Xiaochuang
FANG Qi
XU Zhongxun
FEI Xiang
JIANG Chengbo
ZHANG Xinmiao
YUAN Duanpeng
Related Institution
Henan Pinggao Electric Co., Ltd.
Pinggao Group Co., Ltd.
CSG Extra High Voltage Power Transmission Company, Dali Bureau
China Southern Power Grid Co., Ltd.
State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University