Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer
Research & Analysis|更新时间:2025-04-26
|
Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer
High Voltage ApparatusVol. 60, Issue 12, Pages: 85-94(2024)
作者机构:
1.国网上海市电力公司,上海 200437
2.南瑞集团(国网电力科学研究院)有限公司,南京 211000
3.西安交通大学电气学院,西安 710049
作者简介:
基金信息:
State Grid Corporation of China Technology (Research on Special Test Technology of UHV Converter Transformer Valve Side Bushing)
SI Wenrong, FU Chenzhao, SU Lei, et al. Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer[J]. High voltage apparatus, 2024, 60(12): 85-94.
DOI:
SI Wenrong, FU Chenzhao, SU Lei, et al. Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer[J]. High voltage apparatus, 2024, 60(12): 85-94. DOI: 10.13296/j.1001-1609.hva.2024.12.010.
Research on Electric Field Distribution Characteristics Simulation Under Typical Defects in the Scaled Model of Valve Side Bushing of UHV Converter Transformer
Metal particles mixed into the bushing on the valve side of the converter transformer and cracks in the capacitor core are common faults at present. The research on electric field distribution of the bushing under different voltages and the influence of defects on the electric field distribution are of great significance to the optimization design and failure analysis of the bushing. In this paper
the ±800 kV UHV converter transformer bushing is taken as a prototype
a ±72.5 kV epoxy-impregnated paper capacitive bushing simulation model is set up
the potential and electric field distribution of the bushing under AC and DC voltage is calculated
and the influence of two defects on the electric field is researched. The results show that the bushing
in case of containing metal particles or crack defects
has a greater influence on the distortion of the electric field. The research results not only provide a basis for the subsequent analysis of partial discharge tests of different defects in the scaled bushing model
but also provide a reference for the optimal design of epoxy-impregnated paper capacitive bushing.