Research on Distributed Compensation Strategy of Arc Suppression Coil of 66 kV System
For assuring safe operation of 66 kV resonant grounding system
such two parameters as the damping resistance and the detuning degree of the arc suppression coil need to be reasonably configured. However
the distributed compensation operation makes the parameter setting difficult. In this paper
a kind of decentralized compensation strategy is proposed
which considers such core data as residual current
recovery speed of faulty phase voltage
residual value of the zero-sequence voltage decay after the fault
and the displacement degree. It is obtained by way of experiment that the faulty residual current shall be less than 7 A and the recovery speed of faulty phase voltage shall be lower than 500 V/ms. On this basis
the parameter optimization constraint equation is proposed
and the gradient descent method is used to obtain the maximum value of detuning degree and the minimum value parameters of damping resistance. Finally
an actual 66 kV resonant grounding system is used as an example to verify the effectiveness of the proposed compensation strategy by simulation.