Research on Mechanical Fault Detection Technology of Disconnector Based on Output Power of Motor
High voltage disconnector is widely used in substation
and its operation status has a great impact on safe and stable operation of power grid. However
it is likely to occur various mechanical defects due to long term exposure to the outdoor environment. In this paper
a kind of mechanical fault detection technology of disconnector based on output power of motor is proposed. The input power of the motor is obtained by detecting the voltage and current of the motor during the operation of the disconnector. The output power of the motor is obtained by subtracting the power loss during internal transmission of the motor
which can effectively avoid the influence of the motor power loss on the test results. The typical waveform of four kinds of disconnectors at 110 kV and above
which are commonly used in power system
are analyzed to confirm the positions of waveform peaks and troughs and corresponding mechanical states of each section
provide guidance for subsequent mechanical fault diagnosis and its effectiveness is verified by field test.