HU Yangmu, XIE Qiang. Vibration Response Measurement and Control of Reactors Installed on the Floor[J]. High voltage apparatus, 2025, 61(4): 177-186.
DOI:
HU Yangmu, XIE Qiang. Vibration Response Measurement and Control of Reactors Installed on the Floor[J]. High voltage apparatus, 2025, 61(4): 177-186. DOI: 10.13296/j.1001-1609.hva.2025.04.020.
Vibration Response Measurement and Control of Reactors Installed on the Floor
For studying the vibration characteristics of reactor equipment in attached substations and the propagation of the vibration in the structure as well as controlling the structural comfort issues due to the vibration of reactors
in this paper the vibration characteristics of the reactor are experimentally studied through the method of on-site measurement. A finite elem
ent model of the residential building structure of the attached substation is set up and the propagation of the reactor vibration in the structure is analyzed. The structural comfort is evaluated by using the
Z
vibration level and secondary noise. The vibration isolation effects of different types of vibration isolation bearings added to the reactors are simulated and compared. The results show that secondary noise is the main comfort issue under the vibration of reactors
and the research in the paper can provide a reference for the design of reactor vibration isolation bearings.