LIAO Wang, JIANG Juan, CHEN Li. Seismic Responses and Isolation Analysis of the Neutral Point Protection Device in Offshore Substations[J]. High Voltage Apparatus, 2026, 62(6): 172-178.
DOI:
LIAO Wang, JIANG Juan, CHEN Li. Seismic Responses and Isolation Analysis of the Neutral Point Protection Device in Offshore Substations[J]. High Voltage Apparatus, 2026, 62(6): 172-178.DOI: 10.13296/j.1001-1609.hva.2026.06.021.
Seismic Responses and Isolation Analysis of the Neutral Point Protection Device in Offshore Substations
Pillar-type electrical equipment with high seismic vulnerability is installed in the upper modules of offshore platform structures such as offshore stations in wind farms.To investigate the seismic performance of such equipment
a finite element model is set up for the neutral point protection device of the 220 kV main transformer in a real offshore substation in China. The seismic responses analysis of the equipment is performed by the time-history analysis method. The results show that although the stress at the root of the porcelain bushing complies with the specification requirement
yet the low rigidity of the steel plate of the equipment mounting frame leads to excessive local stress at the connection between the disconnector and the steel plate in seismic condition
exists the damage risk and causes indirectly the damage of equipment. After applying base isolation control using isolation bearings to the original equipment
the stress and acceleration responses at critical locations of the equipment
as well as the peak stress of the equipment mounting frame
ZHU Jizhong, GAO Meiyun, XIAO Pengfei, et al.Review of grid integration and operation technologies for large-scale offshore wind power[J]. Electric Power Engineering Technology,2025,44 (5):2-24.
CHENG Yongfeng, ZHU Zhubing, LU Zhicheng, et al.Research state and development of seismic performance of substation electrical equipment[J]. Building Structure,2019,49(s2):356-361.
HE Hailei, GUO Jianbo, XIE Qiang.Vulnerability analysis of power equipments caused by earthquake disaster[J]. Power System Technology,2011,35(4):25-28.
ZHANG Mi, LIU Fei, WANG Bingyuan, et al. Seismic response and optimization design method of 750 kV surge arrester[J]. High Voltage Apparatus,2022,58(8):33-40.
XIE Qiang, BIAN Xiaoxu, XU Junxin.Anti-seismic design method for floor electrical equipment in whole-indoor substation[J]. High Voltage Engineering,2020,46(6):2155-2163.
WEN Bo, NIU Ditao, ZHANG Junfa, et al. Application of isolation technology in high - voltage electrical equipment[J]. Industrial Construction,2009,39(1):36-41.
LU Zhicheng, ZHU Quanjun, CHENG Yongfeng. Vibration isolation technique application and prospect in power apparatus[J]. Electric Power Construction,2009,30(6):87-89.
ALESSANDRI S, GIANNINI R, PAOLACCI F, et al.Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 1:Preliminary tests and analyses[J]. Engineering Structures,2015(98):251-262.
ALESSANDRI S, GIANNINI R, PAOLACCI F, et al.Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 2:Shaking-table test validation[J]. Engineering Structures,2015(98):263-274.
XIE Qiang, WANG Xiaoyou, HU Rong, et al. Shaking table tests on ±800 kV UHV DC wall bushing with damper devices[J]. High Voltage Engineering,2018,44(10):3368-3374.
HE Chang, XIE Qiang, YANG Zhenyu, et al. Seismic performance evaluation and improvement of ultra-high voltage wall bushingvalve hall system[J]. Journal of Constructional Steel Research,2019 (154):123-133.
YANG Zhenyu, XIE Qiang, HE Chang, et al. Isolation design for slender ultra-high-voltage composite equipment using modal parameters considering multiple responses[J]. Engineering Structures,2019(200):109709.
CHEN Quanjie, LIU Hong, ZHENG Hongyu, et al. Review of research progress on seismic isolation technology for electrical power equipment in transformer substations[C]//Conference on Industrial Construction 2020. Beijing:Industrial Construction, 2020:192-201.
WANG Zhe, ZHU Peng, SHI Gaoyang. Simulation analysis on seismic responses and vibration control of 110 kV disconnector[J]. High Voltage Apparatus,2022,58(8):196-203.
电力设施抗震设计规范:GB 50260—2013[S].2013.
Code for seismic design of power facilities:GB 50260—2013[S].2013.
IEEE recommended practice for seismic design of substations :IEEE 693:2018[S].2018.
GUAN Zhenzhen, ZHU Quanjun, FAN Xiying, et al. Study on Chinese, American and European codes for seismic design of electrical installations[J]. Earthquake Engineering and Engineering Vibration,2018,38(3):184-193.
CHENG Yongfeng, DAI Zebing, LU Zhicheng, et al. Study on method of seismic design for electrical equipment with energy dissipation devices in China[J]. High Voltage Apparatus,2013,49 (9):67-73.
建筑隔震橡胶支座:JG/T 118—2018[S].2018.
Rubber isolation bearings for buildings:JG/T 118—2018[S].2018.