LI Qiang, LIU Wei, ZHANG Yanchao, et al. Research on Arc Voltage Characteristics and Direct Current Interruption Performance of Vacuum Switch with Different Magnetic Field Configurations[J]. High Voltage Apparatus, 2026, 62(9): 43-49,59.
DOI:
LI Qiang, LIU Wei, ZHANG Yanchao, et al. Research on Arc Voltage Characteristics and Direct Current Interruption Performance of Vacuum Switch with Different Magnetic Field Configurations[J]. High Voltage Apparatus, 2026, 62(9): 43-49,59.DOI: 10.13296/j.1001-1609.hva.2026.09.005.
Research on Arc Voltage Characteristics and Direct Current Interruption Performance of Vacuum Switch with Different Magnetic Field Configurations
In this paper the arc voltage characteristics and DC performance of vacuum arcs under different magnetic field configurations are researched
and the influence patterns of various magnetic field configurations on the DC interruption capability and arc voltage evolution during arcing process are obtained. The DC interruption performance of vacuum arcs under different magnetic filed configurations is experimentally investigated. The results show that the falt-type contact subjected to a pulse transverse magnetic field exhibits the strongest DC interruption capability
achieving a maximum interruption capacity of 900V/900 A. Under the action of a pulsating transverse magnetic field
the flat contact configuration successfully achieves DC interruption at 400 V/400 A. In contrast
DC interruption capability of both the axial magnetic field contac and the spiral-groove contacts exhibit weak inferior DC interruption capabilities and are unable to interrupt DC current. The variation of arc voltage during vacuum arc interruption under diverse magnetic field configurations are compared and analyzed. The result shows that the arc voltage during DC vacuum interruption under transverse magnetic field presents severe instability and is prone to intense oscillations. Violent oscillations occur in the arc voltage of transverse magnetic field contacts throughout the arcing period. In particular
for flat contacts with externally applied transverse magnetic field under a current of 8 kA
the peak oscillation amplitude of arc voltage reaches up to 250 V.
Wang Lu. Accelerated construction of new-type power system during the critical period of the 15th five-year plan[N]. Economic Reference News. 2025-09-30(003).
Zhu Jizhong,Gao Meiyun,Xiao Pengfei,et al. Review of grid integration and operation technologies for large-scale offshore wind power[J]. Electric Power Engineering Technology,2025,44(5):2-24.
Huang Yongrui,Han Kun,Hu Qiuling,et al. Suppression of AC overvoltage at sending end under DC transmission system fault based on controllable energy dissipation[J]. Electric Power Engineering Technology,2025,44(4):138-146.
Cao Xunzhe,Li Fengting,Yin Chunya,et al. Low voltage crossing strategy for all-DC power generation system of onshore wind power based on battery energy storage[J]. Electric Power Engineering Technology,2025,44(3):150-159.
Huang Qiang,Li Kuan,Fan Rongqi,et al. A grid side fault ridethrough control for renewable energy connectedMMC-HVDC[J]. Electric Power Engineering Technology,2025,44(6):165-173.
江道灼,郑欢.直流配电网研究现状与展望[J].电力系统自动化,2012,36(8):98-104.
Jiang Daozhuo,Zheng Huan. Research status and developing prospect of DC distribution network[J]. Automation of Electric Power Systems,2012,36(8):98-104.
Fang Chaolin,Xu Zhihong. No-arc control strategy of AC/DC contactor based on hybrid commutation technology[J]. Proceedings of the CSEE,2019,39(8):2468-2476.
Slade P G. The vacuum interrupter:theory,design,and application[M]. Boca Raton:CRC Press,2008:293-296.
Liu Zhiyuan,Wang Jimei,Xiu Shixin,et al. Development of highvoltage vacuum circuit breakers in China[J]. IEEE Transactions on Plasma Science,2007,35(4):856-865.
Liu Xiaoming,Zhao Yuanyuan,Chen Hai,et al. Analysis of influencing factors of arc motion characteristics of DC transverse magnetic vacuum interrupter[J]. Chinese Journal of Vacuum Science and Technology,2025,45(3):197-204.
Liu Shan,Yuan Zhao,Liu Liming,et al. Experimental study on the initial contraction process of vacuum arc drawing[J]. High Voltage Apparatus,2023,59(6):33-39.
Niwa Y,Palad R,Sasage K,et al. Vacuum arc behavior in transversal magnetic field electrode of vacuum interrupter[C]//201225th International Symposium on Discharges and Electrical Insulation in Vacuum (ISDEIV),2012:505-508.
Wolf C,Kurrat M,Lindmayer M,et al. Arcing behavior on different TMF contacts at high-current interrupting operations[J]. IEEE Transactions on Plasma Science,2011,39(6):1284-1290.
Hanashiro S,Nikadori Y,Kaneko E. Investigation on small DC vacuum arc characteristic under transverse magnetic field[C]//2016 International Conference on Electric Power Equipment-Switching Technology (ICEPE-ST),2016:138-141.
Emtage P R,Kimblin C W,Gorman J G,et al. Interaction between vacuum arcs and transverse magnetic fields with application to current limitation[J]. IEEE Transactions on Plasma Science,1980, 8(4):314-319.
Ma H,Wang J,Liu S,et al. Vacuum arc transient behaviors and voltage characteristics in low - current DC interruption under rotating TMF[J]. AIP Advances,2020,10(8):085018.
Schulman M B,Schellekens H. Visualization and characterization of high-current diffuse vacuum arcs on axial magnetic field contacts[J]. IEEE Transactions on Plasma Science,2000,28(2):443-451.
Schulman M B,Bindas J A. Evaluation of AC axial magnetic fields needed to prevent anode spots in vacuum arcs between opening contacts[J]. IEEE Transactions on Components,Packaging,and Manufacturing Technology:Part A,1994,17(1):53-57.
Watanabe K,Kaneko E,Yanabu S. Technological progress of axial magnetic field vacuum interrupters[J]. IEEE Transactions on Plasma Science,1997,25(4):609-616.