HONG Jian-shan, GUAN Yong-gang, XU Guo-zheng. Influence on Recovery Voltage of High-voltage Circuit Breakers under Different Fault by Employing Series Resonance Type Fault Current Limiter[J]. High voltageapparatus, 2009, 45(5): 24-27.
HONG Jian-shan, GUAN Yong-gang, XU Guo-zheng. Influence on Recovery Voltage of High-voltage Circuit Breakers under Different Fault by Employing Series Resonance Type Fault Current Limiter[J]. High voltageapparatus, 2009, 45(5): 24-27.DOI:
Influence on Recovery Voltage of High-voltage Circuit Breakers under Different Fault by Employing Series Resonance Type Fault Current Limiter
The influence of the series resonance type fault current limiter(SRFCL) on the recovery voltage of circuit breakers after breaking different kind of short-circuit fault was researched and analyzed by using the software of electromagnetic transient simulation ATP-EMTP for the application of SRFCL in 500 kV supergrid.The results show that the rate of rise of recovery voltage(RRRV) increased 18% and the first reference voltage increased 2.6% when circuit breaker breaking outlet short-circuit fault after the SRFCL installed.Under the condition of 90% and 75% rated short-circuit breaking current
the starting part of RRRV decreased 19.26% and 25.6%
and the peak voltage decreased 11.05% and 15.73% individually when circuit breaker breaking short-line fault.The RRRV increased 13.1 times and the first reference voltage increased 78.5% after the SRFCL installed when circuit breaker breaking bus short-circuit fault.The substantial increase of RRRV will seriously affect the breaking capability of high voltage circuit breakers
which should be considered and resolved before the SRFCL installed in supergrid.