HUO Feng-ming1, CHEN Chun-ying2, ZHEN Li2, et al. Operation and Lectotype of 40.5 kV Vacuum and SF6 Circuit Breaker[J]. High voltageapparatus, 2009, 45(3): 135-137+141.
HUO Feng-ming1, CHEN Chun-ying2, ZHEN Li2, et al. Operation and Lectotype of 40.5 kV Vacuum and SF6 Circuit Breaker[J]. High voltageapparatus, 2009, 45(3): 135-137+141.DOI:
Operation and Lectotype of 40.5 kV Vacuum and SF6 Circuit Breaker
There are 146 failures on 40.5 kV circuit breaker in the corporation of China in 2005.The failure rate is 0.304 units per hectounit one year which goes up fastest among all the voltage classes;it takes 21.13% among all the failures and goes up 176.3% against year 2004.There are 14 failures on 40.5 kV vacuum and SF6 circuit breaker only in southern electric power system of Hebei.There have occurred many problems on 40.5 kV circuit breaker due to factors of design
structure of CB and theory of arc extinction etc.The author analyzed the structure
lectotype and technique reform of switch apparatus and brings out some suggestions according to the failures occurred in corporation of China and southern electric power system of Hebei.